High Accuracy Integrated Current Transformer for Three Phase Energy Smart Electricity Meter

Product Details
Customization: Available
Application: Electronic, Instrument
Type: Current Transformer
Still deciding? Get samples of US$ 0.5/Piece
Request Sample
Gold Member Since 2024

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

to see all verified strength labels (20)
Find Similar Products

Basic Info.

Model NO.
LSY5-10/135
Phase
Three
Operation Condition
Indoor
Usage
Protection, Measurement
Winding Form
Multilayer Honeycomb Type
Insulating Medium
Epoxy Resin
Installation
Busbar Type
Magnetic Circuit Structure
Combined Type
Voltage Transformation Principle
Capacitive Type
Accuracy Class
0.05, 0.1, 0.2
Application Range
Energy Meter
Max Current
5A-300A
Current Transformer Ratio
1:1000, 1:2000, 1:2500
DC Immunity
DC Immunity
Material
Nano Crystalline, Ferrite Core
Self Heating Testing
Pass Self Heating Testing
DC Tolerance
Good DC Tolerance
Standard
IEC62052-31
Rosh
Rosh Compliant
Transport Package
Carton/ Pallet
Trademark
TOPRO
Origin
China
HS Code
850431
Production Capacity
100000000PCS

Product Description

Product Description

    

    LSY series of three-phase current transformers are suitable for installing in switch-gear and pole top switch, which is used for the measurement and protection of zero-sequence current and three-phase current. It can also can be used to measure and protect the zero sequence current of multiple cables.

 

    CT core and secondary winding are poured with the high-quality epoxy resin in the plastic casing, which is moisture-resistant with stable performance.

 

    According to the different current ratio, accuracy class and rated load, this series has different model. For more details, please refer to the corresponding parameters table of each model.

 

(Note: The above current ratios are for regular type, more specification can be provided according to customers' requirements.)

 


Meaning of model
High Accuracy Integrated Current Transformer for Three Phase Energy Smart Electricity Meter
 

Technical data

Application

Measuring current   transformer

Protection current   transformer

Double winding current transformer

Rated

Primary current

(A)

Accuracy class and rated load (VA)

Accuracy class and rated   load

(VA)

 

Accuracy class and rated load (VA)

0.2S

0.2

0.5S

0.5

10P10

10P5

 

0.2S

0.2

0.5S

0.5

10P10

10P5

50

     

2.5

 

1.5

           

75

 

1.5

2.5

3.75

1.5

1.5

           

100

 

5

5

5

2.5

     

1.5

1.5

 

1.5

150

2.5

10

10

2.5

2.5

   

2.5

2.5

2.5

 

2.5

200

7.5

12.5

12.5

5

3.75

   

2.5

2.5

2.5

 

2.5

300

20

20

20

10

5

 

2.5

2.5

2.5

2.5

2.5

 

400

25

25

7.5

20

6.25

 

2.5

2.5

2.5

2.5

2.5

 

500

30

25

10

30

7.5

 

3.75

3.75

3.75

3.75

3.75

 

600

35

35

25

40

10

 

5

2.5

5

5

5

 

 

 

Outline dimension (mm)
High Accuracy Integrated Current Transformer for Three Phase Energy Smart Electricity Meter

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier